BS 5839-1 and BS 5266-1 were both fully rewritten in 2025 — plenty of templates and habits out there still cite the old editions. Here are the current test and service frequencies, with the exact clauses your paperwork should reference.

Want this as a printable PDF?

Enter your email and it's yours. I'll also hold a Founding 50 place for you — 60 days of EmberSuite Fire free with the £24.99/mo launch price locked for life. No spam, unsubscribe by replying "stop".

Fire detection & fire alarm systems

BS 5839-1:2025

FrequencyWhatWho
WeeklyUser test from a manual call point — rotate through a different call point each week so every MCP is tested over time; confirm sounders are heard and the panel receives the signal. Record in the logbook.Responsible person / trained user
Every 5–7 monthsPeriodic inspection and servicing visit. Successive visits at intervals of between 5 and 7 months — "every 6 months" habits are fine, but the 2025 edition frames it as a 5–7 month window.Competent person (servicing organisation)
As they happenRecord every false alarm with cause, device and action taken — false-alarm management is a core 2025-edition theme.Responsible person

Emergency lighting

BS 5266-1:2025 (with BS EN 50172:2024 / BS EN 1838:2024)

FrequencyWhatWho
MonthlyShort function test of all luminaires and exit signs — confirm each lamp operates on switching to emergency power. Record areas checked and failures.Responsible person / trained user
AnnuallyFull rated-duration test (typically 3 hours) — luminaires must last their full rated duration. Record the duration achieved.Competent person
At least every 5 yearsPhotometric performance verification of the installed system, recorded in the emergency lighting logbook.Competent person

Portable fire extinguishers

BS 5306-3:2017

FrequencyWhatWho
MonthlyVisual check — in place, unobstructed, pressure in range, seals intact, no visible damage.Responsible person / user
AnnuallyBasic service of every extinguisher.Competent person
Every 5 yearsExtended service (discharge test and internal inspection) — water, foam, dry powder and wet chemical types.Competent person
Every 10 yearsCO₂ and primary sealed powder units — hydraulic pressure test at an approved centre.Approved centre

Fire doors

Fire Safety (England) Regulations 2022 · BS 9999 for other premises

FrequencyWhatApplies to
QuarterlyChecks of fire doors in communal parts.Residential buildings over 11 m in height
AnnuallyChecks of flat entrance doors (best endeavours to gain access).Residential buildings over 11 m in height
Routine (commonly 6-monthly)Inspection of fire doors as part of general good management per BS 9999 guidance.All other premises

Drills, training & the risk assessment itself

Regulatory Reform (Fire Safety) Order 2005 · Building Safety Act 2022 s.156

FrequencyWhatNotes
At least annually (commonly 6-monthly)Fire / evacuation drill — practise the emergency plan; record evacuation time and areas covered.RRO 2005 art. 15
Induction + refreshersStaff fire safety training, with per-person records and refresher due dates.RRO 2005 art. 21
Review regularly & after material changeThe fire risk assessment — since 1 Oct 2023, s.156 requires the FULL assessment recorded in writing (all findings, not just significant ones), whatever the size of the business. Fines are unlimited.RRO 2005 art. 9 + BSA 2022 s.156

FRA methodology: PAS 79-1:2020 for non-housing premises; BS 9792:2025 for housing.

Every interval above, tracked automatically.

EmberSuite Fire generates the certificates (worded to the current editions), keeps the statutory logbook digitally, and reminds you and your clients before anything lapses. Building owners get their logbook portal free. First 50 accounts: 60 days free, £24.99/mo locked for life.

See the Founding 50 offer →

This cheat sheet is a general summary for guidance only and is not legal advice. Frequencies shown are the standards' baseline recommendations — your fire risk assessment, system category or insurer may require more frequent regimes. Always confirm against the current editions of the standards cited and the Regulatory Reform (Fire Safety) Order 2005. © 2026 EmberSuite Fire.